BF-D215B+, featuring compact construction and rail-mounted design for quick installation, is mainly used to control hot water circulation, water return systems, etc.
The controller enables intelligent detection of the temperature difference between a [high temperature (HT) point (e.g., heat collector)] and a [low temperature (LT) point (e.g., water tank)]. Once the [temperature difference] reaches the user's preset value, the relay output will be automatically activated to control [circulation pumps] and other loads for cooling and heating circulation of HT and LT media to minimize the temperature difference between the HT and LT temperature zones (temperature difference).
BF-D215B+ supports activation only in case of positive temperature difference. No output will be activated if the temperature difference is a negative value.
Thanks to the wide range of rated power supply, the controller is able to ensure stable, reliable and durable operation by adapting to AC80V~240V power supply.
(产品已申请专利,仿冒必究)
Measure the temperature difference between two points, and start one-channel relay output once the set positive temperature difference is reached
Relay output NO/NC contact
Press F1 to view temperature individually at HT/LT point
Manual correction for measured HT/LT temperature value
Memorize the set parameter for a long time after power failure
NTC 240K temperature sensor for stable and reliable measurement
No compensation required for long-distance (100 m) measurement by the temperature sensor
To be mounted on standard guide rail, featuring small size and easy installation.
Switch mode power supply, ensuring stable running with AC80-240V power supply
Packing List of Product |
1. Main unit 2. 2 x NTC (10K) temperature sensing wire 3. User instructions |
Overall Dimensions (mm) |
L 91 × W 40 × H 52 |
Installation and Dimensions (mm) |
The controller can be installed on a standard DIN guide rail or permanently mounted with two fixing holes (hole pitch = 84 mm). |
Weight |
Net weight: 0.188 Kg Gross weight: 0.232 Kg |
Power Supply and Consumption Power |
AC (80~240)V, 2W |
Operating Conditions | -10℃ ~ 50℃ |
Display Mode |
LED digital display |
Keys |
Push-type membrane keys |
Input |
Two-channel 10K NTC thermistor temperature sensor inputs, measuring range: -50~120 ℃ |
Output |
1. One-channel relay NO/NC contact output for temperature difference circulation 2. Current capacity of output contact: 5 A (resistive load) and 1 A (inductive load) Able to control 1000W electric heating equipment or 200W motors or water pumps. AC contactors should be used to increase the capacity for larger loads. |
Measurement Range |
-50~120 ℃; Measurement range of temperature difference: -99~120℃ |
Setting Range |
0~80 ℃ |
Control Range |
0~80 ℃ |
Other Parameters |
1. Temperature sensing wire can be extended by 100 m with ordinary wire for long-distance connection. 2. Memorize the set parameter for a long time after power failure 3. Temperature control hysteresis: 0 ℃~30 ℃. |
Welcome your suggestions, please fill in the form below to send your message.
Legal statement: our products have applied for a patent or are in the process of patent application, all products are our company's research and development, we have all products of the program source code and the original design information, any copying and counterfeiting, once found, will be subject to legal action! Advocate originality, resist imitation.