BF-D215B+, featuring compact construction and rail-mounted design for quick installation, is mainly used to control hot water circulation, water return systems, etc.

The controller enables intelligent detection of the temperature difference between a [high temperature (HT) point (e.g., heat collector)] and a [low temperature (LT) point (e.g., water tank)]. Once the [temperature difference] reaches the user's preset value, the relay output will be automatically activated to control [circulation pumps] and other loads for cooling and heating circulation of HT and LT media to minimize the temperature difference between the HT and LT temperature zones (temperature difference).

BF-D215B+ supports activation only in case of positive temperature difference. No output will be activated if the temperature difference is a negative value.

Thanks to the wide range of rated power supply, the controller is able to ensure stable, reliable and durable operation by adapting to AC80V240V power supply.

(产品已申请专利,仿冒必究)

Installation and Features

                                                      (产品已申请专利,仿冒必究)

Main Features

  • Measure the temperature difference between two points, and start one-channel relay output once the set positive temperature difference is reached

  • Relay output NO/NC contact

  • Press F1 to view temperature individually at HT/LT point

  • Manual correction for measured HT/LT temperature value

  • Memorize the set parameter for a long time after power failure

  • NTC 240K temperature sensor for stable and reliable measurement

  • No compensation required for long-distance (100 m) measurement by the temperature sensor

  • To be mounted on standard guide rail, featuring small size and easy installation.

  • Switch mode power supply, ensuring stable running with AC80-240V power supply

Specifications and Technical Data

Packing List of Product

1. Main unit

2. 2 x NTC (10K) temperature sensing wire

3. User instructions

Overall Dimensions (mm)

L 91 × W 40 × H 52

Installation and Dimensions (mm)

The controller can be installed on a standard DIN guide rail or permanently mounted with two fixing holes (hole pitch = 84 mm).

Weight

Net weight: 0.188 Kg  

Gross weight: 0.232 Kg

Power Supply and Consumption Power

AC (80240)V, 2W

Operating Conditions

-10℃ ~ 50℃

Display Mode

LED digital display

Keys

Push-type membrane keys

Input

Two-channel 10K NTC thermistor temperature sensor inputs, measuring range: -50120

Output

1. One-channel relay NO/NC contact output for temperature difference circulation 

2. Current capacity of output contact: 5 A (resistive load) and 1 A (inductive load)

Able to control 1000W electric heating equipment or 200W motors or water pumps. AC contactors should be used to increase the capacity for larger loads.

Measurement Range

-50120 ; Measurement range of temperature difference: -99120

Setting Range

080

Control Range

080

Other Parameters

1. Temperature sensing wire can be extended by 100 m with ordinary wire for long-distance connection.

2. Memorize the set parameter for a long time after power failure  

3. Temperature control hysteresis: 0 ℃30 ℃.


Power Supply and Input & Output Ports





Welcome your suggestions, please fill in the form below to send your message.

Legal statement: our products have applied for a patent or are in the process of patent application, all products are our company's research and development, we have all products of the program source code and the original design information, any copying and counterfeiting, once found, will be subject to legal action! Advocate originality, resist imitation.